A firewall between IT and OT is not segmentation

The claim

A firewall between IT and OT is a boundary. Segmentation is a model. The firewall describes what may pass between two networks, and it says nothing at all about what may move around inside it. If everything behind the first door reaches everything else, you have a door, not a segmentation model.

The difference is invisible as long as nothing happens, and decisive the day something is already inside: a service laptop, a supplier connection, a device commissioned with the manufacturer’s default settings. At that point the extent of the damage is determined by what the network looks like behind the firewall, not by how the firewall’s rule set is written. A firewall is a necessary component of a segmentation model. It is not the model.

What segmentation does

The same intrusion, two network models.

Choose network model
← FIELD EQUIPMENTBUSINESS SYSTEMS →ZONE 1 — PROCESSRTU · METERS · PROTECTIONZONE 2 — CONTROLENERGY MANAGEMENT · REGULATIONZONE 3 — OPERATIONSSCADA · HISTORIAN · ALARMSSTOPPEDZONE 1 — PROCESSRTU · METERS · PROTECTIONZONE 2 — CONTROLENERGY MANAGEMENT · REGULATIONZONE 3 — OPERATIONSSCADA · HISTORIAN · ALARMSSTOPPED↑ BUSINESS SYSTEMS↓ FIELD EQUIPMENT

Flat network. One compromised device on the process network reaches everything, operations monitoring included. That takes minutes, not days.

Zoned network. The same intrusion stays in the zone where it started. The damage is bounded, and the logs show where the boundary held.

fig. 1Spread of an intrusion in a flat and a zoned network. Switch between the two.

What IEC 62443 actually says

IEC 62443-3-2 describes a method rather than a product. The standard establishes requirements for defining a system under consideration (SUC) for an industrial automation and control system, partitioning that system into zones and conduits, assessing the risk for each zone and conduit, establishing a target security level (SL-T) for each of them, and documenting the security requirements. This was checked against IEC’s own publication record in September 2026.

Three concepts carry the whole argument.

A zone is, in IEC’s wording, a grouping of assets based on risk. Not on technology, not on supplier, not on which switch they happen to sit in. Two systems belong in the same zone when they can live with the same level of protection, and when it is reasonable to assume that compromise of one means the other is lost as well. That is why zoning is risk work before it is network work.

A conduit is the communication between zones. The important point is that a conduit is a design object in its own right, with its own security requirements and its own target level — not whatever happens to be left over once the zones have been drawn. Every conduit should be justifiable: which function requires it, and what stops working if it is closed.

Security levels SL 1–4 tie the set of countermeasures to the strength of the adversary you intend to withstand, so that different zones can be protected to different degrees without the difference being arbitrary. And among the series’ seven foundational requirements there is one that addresses precisely this: FR 5, restricted data flow. Segmentation is therefore not an interpretation of IEC 62443. It is one of the standard’s foundational requirements.

Why flat OT networks are the normal case

An effectively flat operational network behind the IT/OT boundary is the normal case in the industry. This is not negligence. It is history.

Station LANs were built for determinism and availability, not to withstand an adversary who is already inside. The migration from serial protocols to IP suddenly gave IP connectivity to equipment that was never designed to sit on a routed network. Every new integration — historian, remote support, analytics, meter values into the finance system — has been added one at a time, each for a defensible reason, and none of them on its own has justified a redesign. That is the normal situation, not the exception.

What to do first

Discovering that you have a flat OT network often leads to the wrong first action: a procurement of more firewalls. The order should be a different one.

  1. Draw the boundary. Decide what is inside the system you are analysing. A system under consideration without a boundary cannot be assessed, and most segmentation projects that stall did so because the scope was never fixed.
  2. Map flows, not only assets. An inventory tells you what exists. A flow map tells you what talks to what, and it is the flow map that determines where a zone can be placed. Collect passively.
  3. Group by consequence. Ask what happens to the process if a given group is lost. Systems with the same answer belong together. Which supplier delivered them is irrelevant to the partitioning.
  4. Name the conduits. For each pair of zones: which communication is required, by which function, and in which direction. Anything that does not make the list is a candidate for removal, and that list is usually shorter than the network suggests.
  5. Set the target level and be honest about today. The gap between the desired and the achieved level per zone is your action plan, and it is also the material a supervisory authority will ask for.
  6. Start where the process is not affected. Remote access, engineering workstations and the separation between operations and administration can almost always be addressed without touching control. That produces a visible effect within a single maintenance window.

For anyone within the scope of cybersäkerhetslagen — the Swedish Cybersecurity Act (SFS 2025:1506), implementing NIS2 — there is a timing argument as well. The regulations on security measures and management training (MCFFS 2026:11) take effect on 1 October 2026 and rest on a risk-based approach, in which the operator is expected to identify and manage its own risks. A risk-based approach presupposes knowing what the risks are. In practice, a flow map is a precondition for being able to answer.

What is difficult

Zones rarely follow organisational boundaries. The line a risk assessment wants to draw often runs straight through a service agreement. Closing a conduit may mean a supplier can no longer reach its own equipment, at which point it is no longer a network decision but a commercial negotiation. Expect that part to take the time.

Availability cannot be negotiated away. You cannot stop the process in order to rebuild. IEC 62443 therefore allows compensating countermeasures where a requirement cannot be implemented directly — particularly for legacy systems — and that is often the right route. It presupposes that the deviation is documented as a deliberate choice with a compensating measure, rather than quietly dropped.

Zones on paper are more dangerous than no zones. A zone diagram that is not enforced in the configuration will still be cited at audit and in incident assessment. Our position is that a zone does not exist until the separation has been verified by test, and that the verification has to be repeated — configurations drift.

Some industrial communication patterns do not tolerate arbitrary filtering. Fine-grained segmentation inside a control system can disturb functions that depend on a particular traffic pattern. GOOSE and Sampled Values in IEC 61850 are the example: time-critical layer 2 multicast that, in its basic form, does not cross a routed boundary and tolerates very little delay. It is a reason to begin with the outer conduits and work inwards, rather than the other way around.